1 Application range
This series of integrated relays for opening, closing and power monitoring are used in various automatic control or relay protection circuits. They can directly control the opening and closing circuits, monitor and control the power supply, and can conveniently adjust the closing delay and power supply. Monitor the power-off delay time.
2 Model definition

3 main performance
3.1 The integrated relay combines the three independent functional circuits of the power monitoring circuit, the instantaneous opening circuit, and the delay closing circuit to save on-site installation space.
3.2 Adopt sealed relay, moisture-proof, dust-proof, uninterrupted wire, high reliability.
3.3 Instantaneous circuit, fast action and return time.
3.4 Delay loop, the delay time can be set with the dial switch on the panel.
3.5 After each circuit of the relay operates, there are light instructions respectively, which are clear and clear.
3.6 The electrical and mechanical life of the relay is long.
3.7 Large contact capacity and low contact resistance.
3.8 High insulation withstand voltage level.
4 Technical conditions
4.1 Environmental reference conditions
Environment temperature: 20±2℃
Relative humidity: 45%~75%
Atmospheric pressure: 86~106KPa
4.2 Normal use conditions
Ambient temperature: -10℃~+50℃
Relative humidity of environment: not more than 90%
Atmospheric pressure: 80~110KPa
Limit temperature during storage and transportation: -25℃~+70℃
The altitude of the place of use: no more than 2500 meters
The surrounding medium of the operating environment has no explosion hazard; it does not contain corrosive gas; the concentration of conductive dust contained should not reduce the insulation level below the allowable limit value;
Reliable power supply.
4.3 Characteristic parameters
4.3.1 Rated voltage: 220VDC, 110VDC, 220VAC, allowable fluctuation range of power supply: 0.8~1.15 times the rated voltage.
4.3.2 Action and return time of the instantaneous loop: not more than 20mS.
4.3.3 Delay range and level difference of closing circuit: 0.1~10S, level difference 0.1S;
4.3.4 Delay range and level difference of power monitoring circuit: 0.5S~5S, level difference 0.5S.
4.4 Maximum power consumption
DC voltage type: Under 220VDC, the delay circuit is not more than 7W, and the instantaneous circuit is not more than 3W.
AC voltage type: Under 220VAC, the delay circuit is not more than 7VA, and the instantaneous circuit is not more than 3VA.
4.5 Maximum capacity of contacts:
Cut-off load capacity: DC 250V or less, τ=5ms, inductive load 50W, resistive load 150W;
AC below 250V, load 1200VA;
Allow long-term connection current: 5A.
4.6 Insulation resistance: Use an open-circuit voltage 500V megger to measure the insulation resistance between the exposed non-charged metal parts or shells of the relays connected to each conductive terminal and should not be less than 10MΩ.
4.7 Insulation withstand voltage: each lead-out terminal to the housing locking screw can withstand a power frequency voltage of 2000V, and the same group of contacts can withstand a power frequency voltage of 1000V, which lasts for one minute without breakdown.
4.8 Anti-interference performance: meet the national GB6162-85 "Electrical Interference Test of Static Relays and Protection Devices" standard.
4.9 Electrical life: The contact is more than 104 times under rated load.
4.10 Mechanical life: The contact is 3 million times under no load.
5 Structure type (see the relay structure size diagram for details)
5.1 Protruding board front wiring structure AQ11 rear view wiring diagram (subject to company product samples)
5.2 The wiring structure behind the embedded board AK11, AP11 rear view wiring diagram (subject to company product samples)
6 Use
6.1 Before energizing the relay, confirm whether the voltage level of the connected relay is consistent with the actual parameters, otherwise the relay may be damaged; check whether the relay is damaged during transportation and storage, and the relay screw fasteners should not be loose; if there are damaged parts , Please contact us to replace it for you.
6.2 RZH-11/21, RZH-11/25, RZH-11/26, RZH-12, RZH-21/21 relays will open instantaneously, and the relays will be closed after a delay action. RZH-11/22, RZH-11/23, RZH-11/24, RZH-13, RZH-23, RZH-21/22, RZH-21/23 Relay When the power monitoring circuit monitors the power circuit control power supply loss , After the power-off delay action alarm, at this time the closing circuit also returns instantaneously due to the disappearance of the power supply; if the power supply is normal, the closing circuit will act instantaneously and the power-off delay will return; the opening monitoring circuit will act instantaneously.
6.3 The delay of the power monitoring and closing circuit is set with the dial switch according to the formula on the relay panel.
The power monitoring delay time setting range is 0.5-5S, t=[0.5×□+0.5 ]S
When the closing monitoring delay time setting range is 0.1-10S, t=[□+0.1×□+0.1] S
7 Ordering instructions
When ordering, please specify the relay model, specification, quantity, rated voltage, structure, delay range and other requirements.